References - order by products

United Kingdom, Chathill Sewage Works

Object
Sewage Treatment Plant in Chathill. Repair to Leaking Sewage Tank. 
Fields of application
Pressure injection of water bearing cracks
Description
The aim was to stop a leak within an 8 metre deep sewage tank. The tank was constructed with cast manhole rings placed inside a plastic liner. The liner subsequently failed resulting in pressurised water ingress through the wall to floor joint. KOSTER Waterstop was used to create a watertight fillet detail around the wall to floor joint and then KOSTER KB PUR IN 7 was injected to stop the pressurized flow of water and create a seal between the plastic liner and the concrete manhole rings.Finally a level, reinforced deck was created using KOSTER Sewer & Shaft Mortar which is fibre reinforced, very strong and designed to work under water. 
Product applied
KÖSTER IN 7
KÖSTER PUR Cleaner
KÖSTER Sewer and Shaft Mortar
KÖSTER Superpacker 13 mm x 130 mm CH
KÖSTER Waterstop
Contractor
St Astier 
Select product:

 

 

Back

Top
Albania Austria Bosnia and Herzegovina Brasil Bulgaria China Croatia Czech Republic Denmark Finland Germany Ghana Greece Hungary Italy Japan Kazakhstan Kuwait Latvia Lebanon Macedonia Mexico Netherlands New Zealand Norway Panama Poland Portugal Romania Russia Senegal Serbia Slovakia Slovenia South Africa Spain Thailand Turkey Ukraine United Kingdom United States of America